Sprinkler fire extinguishing sp 5. Fire protection systems. Fire alarm and fire extinguishing installations are automatic. Design norms and rules. to the order of the Ministry of Emergency Situations of Russia

CHANGE N 1
to the set of rules SP 5.13130.2009 "Systems fire protection. Settings fire alarm and automatic fire extinguishing systems. Design standards and rules"


OKS 13.220.10

Date of introduction 2011-06-20


APPROVED AND PUT INTO EFFECT by order of the Ministry of Emergency Situations of Russia dated 06/01/2011 N 274 from June 20, 2011.

1) In section 3:

clause 3.99

"3.99 sprinkler-drencher AUP (AUP-SD): Sprinkler AUP, in which a deluge control unit and technical means for its activation are used, and the supply of fire extinguishing agent to the protected area is carried out only when the sprinkler is triggered according to the logical “I” circuit and technical means activation of the control node.";

add paragraphs 3.121-3.125 with the following content:

"3.121 fire automatic system: Equipment connected by connecting lines and operating according to a given algorithm in order to perform tasks to provide fire safety on the object.

3.122 air compensator: A fixed orifice device designed to minimize the likelihood of false alarm valve activations caused by air leaks in the supply and/or distribution piping of air sprinkler AUPs.

3.123 irrigation intensity: The volume of fire extinguishing liquid (water, aqueous solution (including an aqueous solution of foaming agent, other fire extinguishing liquids) per unit area per unit time.

3.124 minimum area irrigated by AUP: The minimum value of the normative or design part of the total protected area subject to simultaneous spraying with fire extinguishing liquid when all sprinklers located on this part of the total protected area are activated.

3.125 thermally activated microencapsulated OTV (Terma-OTV): A substance (fire extinguishing liquid or gas) contained in the form of microinclusions (microcapsules) in solid, plastic or bulk materials, released when the temperature rises to a certain (specified) value."

2) Clause 4.2 of Section 4 should be stated as follows:

"4.2 Automatic installations (with the exception of autonomous ones) must simultaneously perform the function of a fire alarm."

3) In section 5:

in the notes to table 5.1 of paragraph 5.1.4:

paragraph 4 should be stated as follows:

"4 If the actual protected area is less than the minimum area irrigated by the AUP specified in Table 5.3, then the actual flow rate can be reduced by a factor.";

add paragraphs 7-9 as follows, respectively:

"7 The duration of operation of foam fire extinguishing systems with low and medium expansion foam for the surface fire extinguishing method should be taken as follows: 10 minutes - for premises of categories B2 and B3 according to fire danger; 15 minutes. - for premises of categories A, B and B1 for explosion and fire hazard; 25 min. - for premises of group 7.

8 For deluge AUPs, it is allowed to place sprinklers with distances between them greater than those given in Table 5.1 for sprinkler sprinklers, provided that when placing deluge sprinklers, the standard values ​​of irrigation intensity for the entire protected area are ensured and the decision made does not contradict the requirements of the technical documentation for this type irrigators.

9 The distance between sprinklers under a sloped roof should be taken along a horizontal plane.";

clause 5.4.4 deleted;

clause 5.8.8

"In sprinkler water-filled and air-filled automatic control systems, it is allowed to install a shut-off device behind the signal valve, provided that automatic control state of the locking device ("Closed" - "Open") with signal output to the room with constant presence of duty personnel.";

clause 5.9.25 shall be supplemented with the following paragraph:

"The design and reserve volumes of the foaming agent may be contained in one vessel."

4) table 8.1 of clause 8.3 of section 8 should be stated as follows:

"Table 8.1

Liquefied gases

Compressed gases

Carbon dioxide ()

Freon 23 ()

Argon()

Freon 125 ()

Freon 218 ()

Freon 227ea ()

nitrogen () - 52% (vol.)

argon () - 40% (vol.)

carbon dioxide () - 8% (vol.)

Freon 318C ()

Sulfur hexafluoride ()

nitrogen () - 50% (vol.)

argon () - 50% (vol.)

Freon TFM-18I:

freon 23 () - 90% (wt.)

methyl iodide () - 10% (mass.)

Freon FK-5-1-12 ()

Freon 217J1 ()

Freon

5) In section 11:

clause 11.1 should be stated as follows:

"11.1 Autonomous fire extinguishing installations are divided by type of fire extinguishing agent (FME) into liquid, foam, gas, powder, aerosol, fire extinguishing installations with Terma-OTV and combined.";

clauses 11.3, 11.4

"11.3 The design of autonomous installations is carried out in accordance with the design guidelines developed by the design organization to protect standard facilities.

11.4 The requirements for the stock of fire extinguishing agents for an autonomous fire extinguishing installation must comply with the requirements for the stock of fire extinguishing agents for an automatic fire extinguishing installation of a modular type, with the exception of autonomous installations with thermally activated microencapsulated fire extinguishing agents.";

add clause 11.6 with the following content:

"11.6 Self-contained fire extinguishing installations are recommended to be used to protect electrical equipment in accordance with technical characteristics electrical equipment."

6) In section 13:

clause 13.1.11 should be stated as follows:

"13.1.11 Fire detectors should be used in accordance with the requirements of this set of rules, other regulatory documents on fire safety, as well as technical documentation for specific types of detectors.

The design of detectors must ensure their safety in relation to the external environment in accordance with the requirements.

The type and parameters of detectors must ensure their resistance to climatic, mechanical, electromagnetic, optical, radiation and other factors external environment in places where detectors are located.";

clause 13.2.2 should be stated as follows:

"13.2.2 Maximum amount and the area of ​​​​premises protected by one address line with addressable fire detectors or addressable devices is determined by the technical capabilities of the receiving and control equipment, the technical characteristics of the detectors included in the line and does not depend on the location of the premises in the building.

Addressable fire alarm loops together with addressable fire detectors can include addressable input/output devices, addressable control modules for addressless loops with addressable fire detectors included in them, short-circuit separators, addressable actuators. The possibility of including addressable devices in an addressable loop and their number are determined by the technical characteristics of the equipment used, given in the manufacturer’s technical documentation.

Address lines of control panels may include address security detectors or addressless security detectors through addressable devices, subject to the provision of the necessary algorithms for the work of firefighters and security systems.";

clause 13.3.6 shall be stated as follows:

"13.3.6 The placement of point heat and smoke fire detectors should be made taking into account the air flows in the protected room caused by the supply and/or exhaust ventilation, while the distance from the detector to vent must be at least 1 m. In the case of using aspirating fire detectors, the distance from the air intake pipe with holes to the ventilation hole is regulated by the amount of permissible air flow for this type of detector in accordance with the technical documentation for the detector.

The horizontal and vertical distance from the detectors to nearby objects and devices, to electric lamps, in any case must be at least 0.5 m. Fire detectors must be placed in such a way that nearby objects and devices (pipes, air ducts, equipment, etc.) prevented the impact of fire factors on the detectors, and sources of light radiation and electromagnetic interference did not affect the preservation of the detector's functionality.";

clause 13.3.8 shall be stated as follows:

"13.3.8 Point smoke and heat fire detectors should be installed in each ceiling compartment with a width of 0.75 m or more, limited by building structures (beams, purlins, slab ribs, etc.) protruding from the ceiling at a distance of more than 0.4 m.

If building structures protrude from the ceiling at a distance of more than 0.4 m, and the width of the compartments they form is less than 0.75 m, the area controlled by fire detectors, indicated in tables 13.3 and 13.5, is reduced by 40%.

If there are protruding parts on the ceiling from 0.08 to 0.4 m, the area controlled by fire detectors, indicated in tables 13.3 and 13.5, is reduced by 25%.

The maximum distance between detectors along linear beams is determined according to tables 13.3 and 13.5, taking into account clause 13.3.10.";

clause 13.15.9 shall be stated as follows:

"13.15.9 Connecting lines made with telephone and control cables that meet the requirements of clause 13.15.7 must have a reserve supply of cable cores and junction box terminals of at least 10%.";

Paragraph one of clause 13.15.14 shall be stated as follows:

"13.15.14 Not allowed joint laying fire alarm loops and connecting lines of fire automatic systems with voltage up to 60 V with lines with voltage of 110 V or more in one box, pipe, harness, closed channel building structure or on one tray.";

Paragraph one of clause 13.15.15 shall be stated as follows:

"13.15.15 In case of parallel open installation, the distance from wires and cables of fire automatic systems with voltage up to 60 V to power and lighting cables must be at least 0.5 m."

7) In section 14:

clause 14.2 shall be stated as follows:

"14.2 Generation of control signals for warning systems of type 1, 2, 3, 4 by equipment smoke protection, general ventilation and air conditioning, engineering equipment participating in ensuring the fire safety of the facility, as well as the formation of commands to turn off the power supply to consumers interlocked with fire automatic systems, may be carried out when one fire detector is triggered that meets the recommendations set out in Appendix P. In this case, no fire detector is installed in the room (part of the room). less than two detectors connected according to the logical “OR” circuit. The placement of detectors is carried out at a distance no greater than the normative one.

When using detectors that additionally meet the requirements of clause 13.3.3 a), b), c), one fire detector may be installed in a room (part of a room).

Clauses 14.4, 14.5 shall be amended as follows, respectively:

"14.4 In a room with round-the-clock presence of on-duty personnel, notifications about the malfunction of monitoring and control devices installed outside this room, as well as communication lines, monitoring and control of technical means of warning people in case of fire and evacuation control, smoke protection, automatic fire extinguishing and other fire protection installations and devices.

The design documentation must identify the recipient of the fire notification to ensure that the tasks in accordance with Section 17 are completed.

At objects of functional hazard class F 1.1 and F 4.1, fire notifications must be transmitted to departments fire department via a duly allocated radio channel or other communication lines in automatic mode without the participation of facility personnel and any organizations broadcasting these signals. It is recommended to use technical means with resistance to electromagnetic interference of at least the 3rd degree of severity according to GOST R 53325-2009.

In the absence of personnel on site leading 24/7 duty, fire notifications must be transmitted to fire departments via a duly allocated radio channel or other communication lines in automatic mode.

At other facilities, if technically possible, it is recommended to duplicate automatic fire alarm signals about fire to fire departments via a duly allocated radio channel or other communication lines in automatic mode.

At the same time, measures must be taken to increase the reliability of fire notifications, for example, the transmission of “Attention”, “Fire” notifications, etc.

14.5 It is recommended that the smoke ventilation system be started from smoke or gas fire detectors, including if a fire extinguishing sprinkler system is used at the facility.

The smoke ventilation system should be started from fire detectors:

if the response time of the automatic fire sprinkler installation is longer than the time required to activate the smoke ventilation system and ensure safe evacuation;

if the fire extinguishing agent (water) of the water fire extinguishing sprinkler installation makes it difficult to evacuate people.

In other cases, smoke ventilation systems may be switched on from a fire extinguishing sprinkler installation."

8) Clause 15.1 of Section 15 should be stated as follows:

"15.1 In terms of the degree of ensuring the reliability of power supply, fire protection systems should be classified as Category I in accordance with the Electrical Installation Rules, with the exception of compressor electric motors, drainage and foam pumps, which belong to Category III of power supply, as well as the cases specified in paragraphs 15.3, 15.4 .

The power supply to fire protection systems for buildings of functional fire hazard class F1.1 with round-the-clock occupancy should be provided from three independent, mutually redundant power sources, one of which should be autonomous electric generators."

9) In Appendix A:

paragraph A.2 should be stated as follows:

"A.2 In this appendix, a building means a building as a whole or a part of a building (fire compartment), separated by fire walls and fire resistant floors of the 1st type.

Under standard indicator room area in Section III of this appendix means the area of ​​part of a building or structure allocated by enclosing structures classified as fire barriers with a fire resistance limit: partitions - not less than EI 45, walls and ceilings - not less than REI 45. For buildings and structures that include there are no parts (premises) allocated by enclosing structures with the specified fire resistance limit; the standard indicator of room area in Section III of this appendix means the area allocated by the external enclosing structures of the building or structure.";

in table A.1:

paragraphs 4, 5 and 6 shall be stated as follows, respectively:

Object of protection

Standard indicator

4 Buildings and structures for cars:

4.1 Closed parking lots

4.1.1 Underground, above-ground 2 floors or more

4.1.2 Above-ground single-story

4.1.2.1 Buildings of I, II, III degrees of fire resistance

At total area 7000 m or more

With a total area of ​​less than 7000 m

4.1.2.2 Buildings of IV fire resistance class, structural fire hazard class C0

With a total area of ​​3600 m or more

With a total area of ​​less than 3600 m

4.1.2.3 Buildings of IV fire resistance class, structural fire hazard class C1

With a total area of ​​2000 m or more

With a total area of ​​less than 2000 m

4.1.2.4 Buildings of IV degree of fire resistance, structural fire hazard class C2, C3

With a total area of ​​1000 m or more

With a total area of ​​less than 1000 m

4.1.3 Mechanical parking buildings

Regardless of area and number of floors

4.2 For Maintenance and repair

5 Buildings with a height of more than 30 m (except for residential buildings and industrial buildings of categories G and D for fire hazard)

Regardless of area

6 Residential buildings:

6.1 Dormitories, specialized residential buildings for the elderly and disabled

Regardless of area

6.2 Residential buildings with a height of more than 28 m

Regardless of area


the footnote "" should be worded as follows:

"AUPS fire detectors are installed in the hallways of apartments and are used to open valves and turn on fans of air pressure and smoke removal installations. Residential premises of apartments in residential buildings with a height of three floors or more should be equipped with autonomous optical-electronic smoke detectors.";

in table A.3:

paragraph 6 should be included in section " Industrial premises", excluding it from the section "Warehouse premises";

paragraph 35 should be stated as follows:

Object of protection

Standard indicator

35 Accommodation premises:

35.1 Electronic computers (computers), automated process control equipment, operating in control systems for complex technological processes, the violation of which affects the safety of people

Regardless of area

35.2 Communication processors (server), archives of magnetic media, plotters, printing information on paper (printer)

24 m or more

Less than 24 m

35.3 To place personal computers on user desktops

Regardless of area




"In the cases provided for in paragraph 8.15.1 of this set of rules, for premises requiring automatic installations gas fire extinguishing it is allowed not to use such installations, provided that all electronic and electrical equipment is protected by autonomous fire extinguishing installations, and an automatic fire alarm is installed in the premises.";

in table A.4:

add paragraph 8 with the following content:

Object of protection

Standard indicator

8 Electrical panels and electrical cabinets (including distribution devices), located in premises of functional fire hazard class F1.1


add a footnote "" with the following content:

“The listed equipment is subject to protection by autonomous fire extinguishing installations.”;

add the following note:

"Note: Electrical installations located on stationary above-ground and underground metro facilities should be protected by autonomous fire extinguishing installations.";

Appendix D should be supplemented with paragraphs D11-D15 with the following content, respectively:

"D.11 Standard volumetric fire extinguishing concentration of TFM-18I freon. The vapor density at 101.3 kPa and 20 °C is 3.24 kg/m.


Table D.11

Name of combustible material

The number of point fire detectors installed in a room is determined by the need to solve two main problems: ensuring high reliability of the fire alarm system and high reliability of the fire signal (low probability of generating a false alarm signal).

First of all, it is necessary to identify the functions performed by the fire alarm system, namely, whether fire protection systems (fire extinguishing, warning, smoke removal, etc.) are triggered by a signal from fire detectors, or whether the system only provides fire alarm in the premises of duty personnel .

If the function of the system is only a fire alarm, then it can be assumed that the negative consequences of generating a false alarm signal are insignificant. Based on this premise, in rooms whose area does not exceed the area protected by one detector (according to Tables 13.3, 13.5), to increase the reliability of the system, two detectors are installed, connected according to the logical “OR” circuit (a fire signal is generated when any one of them is triggered). two installed detectors). In this case, if one of the detectors fails uncontrollably, the second one will perform the fire detection function. If the detector is capable of testing itself and transmitting information about its malfunction to the control panel (meets the requirements of clause 13.3.3 b), c)), then one detector can be installed in the room. In large rooms, detectors are installed at a standard distance .

Similarly, for flame detectors, each point of the protected premises must be controlled by two detectors connected according to the logical “OR” circuit (in paragraph 13.8.3, a technical error was made during publication, therefore, instead of “according to the logical circuit “AND”” one should read “by logical circuit "OR""), or one detector that meets the requirements of clause 13.3.3 b), c).

If it is necessary to generate a control signal for a fire protection system, then during design the design organization must determine whether this signal will be generated from one detector, which is acceptable for the systems listed in clause 14.2, or whether the signal will be generated according to clause 14.1, i.e. e. when two detectors are triggered (logical “AND” circuit).

The use of a logical “AND” circuit makes it possible to increase the reliability of the formation of a fire signal, since a false alarm of one detector will not cause the formation of a control signal. This algorithm is required to control type 5 fire extinguishing and warning systems. To control other systems you can get by alarm signal from one detector, but only if false activation of these systems does not lead to a decrease in the level of human safety and/or unacceptable material losses. The rationale for such a decision should be reflected in the explanatory note to the project. In this case it is necessary to apply technical solutions, allowing to increase the reliability of the formation of a fire signal. Such solutions may include the use of so-called “smart” detectors, which provide analysis of the physical characteristics of fire factors and (or) the dynamics of their change, providing information about their critical state (dustiness, contamination), using the function of re-querying the status of detectors, taking measures to exclude (reducing) the impact on the detector of factors similar to fire factors and capable of causing a false alarm.

If during the design a decision was made to generate control signals for fire protection systems from one detector, then the requirements for the number and placement of detectors coincide with the above requirements for systems that perform only the alarm function. The requirements of clause 14.3 do not apply.

If the fire protection system control signal is generated from two detectors, switched on in accordance with clause 14.1, according to the “AND” logic circuit, then the requirements of clause 14.3 come into force. The need to increase the number of detectors to three, or even four, in rooms with a smaller area controlled by one detector follows from ensuring high reliability of the system in order to maintain its functionality in case of uncontrolled failure of one detector. When using detectors with a self-testing function and transmitting information about their malfunction to the control panel (meets the requirements of clause 13.3.3 b), c)), two detectors can be installed in the room, necessary to implement the “I” function, but on the condition that the operability of the system is maintained by timely replacement of a failed detector.

In large rooms, in order to save the time of formation of a fire signal from two detectors, connected according to the logical “AND” circuit, the detectors are installed at a distance of no more than half the standard one, so that the fire factors reach and trigger the two detectors in a timely manner. This requirement applies to detectors located along walls and to detectors along one of the ceiling axes (at the designer’s choice). The distance between the detectors and the wall remains standard.

Application of GOTV freon 114B2

In accordance with the International Documents for the Protection of the Earth's Ozone Layer (Montreal Protocol on Substances that Deplete the Earth's Ozone Layer and a number of amendments thereto) and Government Resolutions Russian Federation No. 1000 dated December 19, 2000 “On clarifying the deadline for implementing measures of state regulation of the production of ozone-depleting substances in the Russian Federation”, the production of freon 114B2 has been discontinued.

In pursuance of International Agreements and Decrees of the Government of the Russian Federation, the use of freon 114B2 in newly designed installations and installations whose service life has expired is considered inappropriate.

As an exception, the use of freon 114B2 in AUGP is intended for fire protection of particularly important (unique) facilities, with the permission of the Ministry natural resources Russian Federation.

For fire protection of objects with electronic equipment (telephone exchanges, server rooms, etc.), ozone-non-depleting refrigerants 125 (C2 F5H) and 227 ea (C3F7H) are used.

MINISTRY OF THE RUSSIAN FEDERATION FOR CIVIL DEFENSE, EMERGENCIES AND DISASTER ELIMINATION

ORDER

01.06.2011 № 000

Moscow

On approval of amendment No. 1 to the set of rules SP 5.13130.2009 “Fire protection systems. Fire alarm and fire extinguishing installations are automatic. Design standards and rules”, approved by order of the Russian Ministry of Emergency Situations

In accordance with the Federal Law of 01/01/01 “Technical Regulations on Fire Safety Requirements” (Collection of Legislation of the Russian Federation, 2008, No. 30 (Part 1), Article 3579), Decree of the President of the Russian Federation of 01/01/01 No. 000 “Issues of the Ministry of the Russian Federation for Civil Defense, emergency situations and liquidation of the consequences of natural disasters" (Collected Legislation of the Russian Federation, 2004, No. 28, Art. 2882; 2005, No. 43, Art. 4376; 2008, No. 17, Art. 1814, No. 43, Art. 4921, No. 47, Art. 5431; 2009, art. 2697, no. 6285; 2010, no. 2301, no. 1, Art. 193, Art. 194, No. 2, Art. 267), Decree of the Government of the Russian Federation dated 01.01.01 No. 000 “On the procedure for developing and approving sets of rules” (Collection of Legislation of the Russian Federation, 2008, No. 48 Art. 5608) and in order to ensure compliance of certain provisions (requirements, indicators) of the set of rules SP 5.13130.2009 with the interests of the national economy, the state of the material and technical base and scientific progress, I order:

Approve and put into effect from June 20, 2011 the attached amendment No. 1 to the set of rules SP 5.13130.2009 “Fire protection systems. Fire alarm and fire extinguishing installations are automatic. Design norms and rules”, approved by order of the Russian Ministry of Emergency Situations.


Director of the Administrative Department

Application

to the order of the Ministry of Emergency Situations of Russia

from 01.06.11 No. 000

Change #1

to SP 5.13130.2009

OKS 13.220.01

CHANGE No. 1 to the set of rules SP 5.13130.2009 “Fire protection systems. Fire alarm and fire extinguishing installations are automatic. Design norms and rules"

Regardless of area and number of floors

4.2 For maintenance and repair

Object of protection

Standard indicator

5 Buildings with a height of more than 30 m (except for residential buildings and industrial buildings of categories G and D for fire hazard)

Regardless of area

6 Residential buildings:

6.1 Dormitories, specialized residential buildings for the elderly and disabled1)

Regardless of area

6.2 Residential buildings with a height of more than 28 m 2)

Regardless of area

footnote “2)” should be worded as follows:

“2) AUPS fire detectors are installed in the hallways of apartments and are used to open valves and turn on fans of air supply and smoke removal units. Residential premises of apartments in residential buildings with a height of three floors or more should be equipped with autonomous optical-electronic smoke detectors.”; in table A.Z:

clause 6 should be included in the section “Production premises”, excluding it from the section “Warehouse premises”;

paragraph 35 should be stated as follows:

Object of protection

Standard indicator

35 Accommodation premises:

35.1 Electronic computers (computers), automated process control equipment, operating in control systems for complex technological processes, the violation of which affects the safety of people5)

Regardless of area

35.2 Communication processors (server), archives of magnetic media, plotters, printing information on paper (printer)5)

24 m2 or more

Less than 24 m2

35.3 To place personal computers on user desktops

Regardless of area

add footnote “5)” with the following content:

“5) In the cases provided for in paragraph 8.15.1 of this set of rules, for premises requiring automatic gas fire extinguishing installations, it is allowed not to use such installations, provided that all electronic and electrical equipment is protected by autonomous fire extinguishing installations, and an automatic fire extinguishing system is installed in the premises signaling."; in table A.4:

add paragraph 8 with the following content:

add footnote “1)” with the following content:

“The listed equipment is subject to protection by autonomous fire extinguishing installations.”;

add the following note:

“Note: Electrical installations located on stationary above-ground and underground metro facilities should be protected by autonomous fire extinguishing installations.”;

Appendix D should be supplemented with paragraphs D11-D15 with the following content, respectively:

GOST, TU, OST

D. 12 Standard volumetric fire extinguishing concentration of freon CF3CF2C(0)CF(CF3)2.

The vapor density at P = 101.3 kPa and T = 20 °C is 13.6 kg/m3.

UDC 614.841.3:006.354 OKS 13.220.01

Key words: fire spread, protection objects, public buildings, industrial and warehouse buildings, high-rise buildings

Head of the Federal State Institution VNIIPO EMERCOM of Russia

Head of the Research Center for PP and PChSP FGU VNIIPO EMERCOM of Russia

Head of Development

Performers

Leading researcher at the Federal State Institution VNIIPO EMERCOM of Russia

Name of combustible material

GOST, TU, OST

Standard volumetric fire extinguishing concentration, % (vol.)

D. 13 Standard volumetric fire extinguishing concentration of freon 217J1 (C3F7J).

The vapor density at P = 101.3 kPa and T-20 °C is 12.3 kg/m3.

Name of combustible material

GOST, TU, OST

Standard volumetric fire extinguishing concentration, % (vol.)

D. 14 Standard volumetric fire extinguishing concentration of freon CF3J. The vapor density at P = 101.3 kPa and T = 20 °C is 8.16 kg/m3.

Name of combustible material

GOST, TU, OST

Standard volumetric fire extinguishing concentration, % (vol.)

D. 15 Standard volumetric fire extinguishing concentration of the Argonite gas composition (nitrogen (N2) - 50% (vol.); argon (Ar) - 50% (vol.).

The vapor density at P - 101.3 kPa and T - 20 °C is 1.4 kg/m3.

Name of combustible material

GOST, TU, OST

Standard volumetric fire extinguishing concentration, % (vol.)

Note - The standard volumetric fire extinguishing concentration of the above listed gas extinguishing agents for extinguishing a class A2 fire should be taken equal to the standard volumetric fire extinguishing concentration for extinguishing n-heptane.”;

OKS 13.220.10 UDC614.844.4:006.354

Key words: autonomous fire extinguishing installation, automatic fire alarm, fire extinguishing agent, protected object

Head of the development organization FGU VNIIPO EMERCOM of Russia

Boss

FGU VNIIPO EMERCOM of Russia

Head of Development

Head of Research Center PST

FGU VNIIPO EMERCOM of Russia

Performers

Head of Department 2.4 FGU VNIIPO EMERCOM of Russia

Head of Department 3.4 FGU VNIIPO EMERCOM of Russia

Deputy Head of Department 2.3 FGU VNIIPO EMERCOM of Russia

© "EMERCOM of Russia" 2011

MINISTRY OF THE RUSSIAN FEDERATION FOR CIVIL DEFENSE, EMERGENCIES AND DISASTER ELIMINATION

SET OF RULES

SP 5.13130 ​​as amended 2016

Official publication

Preface

The goals and principles of standardization in the Russian Federation are established by Federal Law No. 184-FZ of December 27, 2002 “On Technical Regulation”, and the rules for applying sets of rules are established by the Decree of the Government of the Russian Federation “On the procedure for developing and approving sets of rules” dated November 19, 2008 No. 858

Rulebook Details

1 DEVELOPED BY FGU VNIIPO EMERCOM of Russia

2 INTRODUCED by the Technical Committee for Standardization TC 274 “Fire Safety”

4 REGISTERED by the Federal Agency for Technical Regulation and Metrology

5 INTRODUCED FOR THE FIRST TIME

Information about changes to this set of rules is published in the annually published information index “National Standards”, and the text of changes and amendments is published in the monthly published information index “National Standards”. In case of revision (replacement) or cancellation of this set of rules, the corresponding notice will be published in the monthly published information index “National Standards”. Relevant information, notices and texts are also posted in information system common use- on the official website of the developer (FGU VNIIPO EMERCOM of Russia) on the Internet

EMERCOM of Russia, 2009 FGU VNIIPO EMERCOM of Russia, 2009

This set of rules cannot be fully or partially reproduced, replicated and distributed as an official publication on the territory of the Russian Federation without the permission of the Ministry of Emergency Situations of Russia and the Federal State Institution VNIIPO EMERCOM of Russia

1 Scope of application...................1

3 Terms and definitions...................3

4 General provisions....................9

5 Water and foam fire extinguishing systems....................................10

6 Fire extinguishing installations with high-expansion foam....................................27

7 Robotic fire complex...................28

8 Gas fire extinguishing installations....................................30

9 Settings powder fire extinguishing modular type......................37

10 Aerosol fire extinguishing installations...................................39

11 Autonomous fire extinguishing installations...................................43

12 Control equipment for fire extinguishing installations.................................43

13 Fire alarm systems................................48

14 Interrelation of fire alarm systems with other systems and engineering equipment of facilities.................................59

15 Power supply for fire alarm systems and fire extinguishing installations.................................60

16 Protective grounding and zeroing. Safety requirements...................61

17 General provisions taken into account when choosing technical means of fire automatics......62

Appendix A List of buildings, structures, premises and equipment subject to

protection by automatic fire extinguishing installations and automatic fire alarms....................................63

Appendix B Groups of premises (production and technological processes) according to the degree of danger of fire development depending on their functional purpose

and fire load of combustible materials...................................70

Appendix B Methodology for calculating the parameters of the fire control system for surface fire extinguishing with water

and low-expansion foam......................71

Appendix D Methodology for calculating the parameters of high-expansion fire extinguishing installations

foam...................79

Appendix E Initial data for calculating the mass of gaseous fire extinguishing agents...................................80

Appendix E Methodology for calculating the mass of gaseous fire extinguishing agent for installations

gas fire extinguishing when extinguishing by volumetric method...................................83

Appendix G Methodology for hydraulic calculation of carbon dioxide fire extinguishing installations

low pressure......85

Appendix 3 Methodology for calculating the opening area for relieving excess pressure in rooms protected by gas fire extinguishing installations......88

Appendix I General provisions for the calculation of modular type powder fire extinguishing installations...................................89

Appendix K Calculation method automatic installations aerosol fire extinguishing........................92

Appendix L Methodology for calculating excess pressure when supplying fire extinguishing aerosol

into the room...................96

Appendix M Selection of types of fire detectors depending on the purpose of the protected premises and the type of fire load....................................97

Appendix N Installation locations of manual fire call points depending on their purpose

buildings and premises...................98

Appendix O Determination of the set time for detecting a malfunction and its

elimination...................99

Appendix P Distances from the top point of the ceiling to the measuring element of the detector..................................... 100

Appendix P Methods for increasing the reliability of a fire signal..................................... 101

Bibliography.........................102

SET OF RULES

Fire protection systems

AUTOMATIC FIRE ALARM AND FIRE FIGHTING INSTALLATIONS

Design standards and rules

Systems of fire protection.

Automatic fire-extinguishing and alarm systems. Designing and regulations.

Date of introduction 2009—05—01

1 area of ​​use

1.1 This set of rules has been developed in accordance with Articles 42, 45, 46, 54, 83, 84, 91, 103, 104, 111-116 Federal Law dated July 22, 2008 No. 123-FZ “Technical regulations on fire safety requirements”, is normative document on fire safety in the field of standardization of voluntary use and establishes norms and rules for the design of automatic fire extinguishing and alarm systems.

1.2 This set of rules applies to the design of automatic fire extinguishing and fire alarm systems for buildings and structures for various purposes, including those built in areas with special climatic and natural conditions. The need to use fire extinguishing and fire alarm systems is determined in accordance with Appendix A, standards, codes of practice and other documents approved in the prescribed manner.

1.3 This set of rules does not apply to the design of automatic fire extinguishing and fire alarm systems:

Buildings and structures designed according to special standards,

Technological installations located outside buildings,

Warehouse buildings with mobile shelving,

Warehouse buildings for storing products in aerosol packaging,

Warehouse buildings with a cargo storage height of more than 5.5 m.

1.4 This set of rules does not apply to the design of fire extinguishing installations for extinguishing class D fires (according to GOST 27331), as well as chemically active substances and materials, including:

Reacting with a fire extinguishing agent with an explosion (organoaluminum compounds, alkali metals),

Decomposes when interacting with a fire extinguishing agent, releasing flammable gases (organolithium compounds, lead azide, aluminum, zinc, magnesium hydrides),

Interacting with a fire extinguishing agent with a strong exothermic effect (sulfuric acid, titanium chloride, thermite),

Self-igniting substances (sodium hydrosulfite, etc.).

1.5 This set of rules can be used when developing special technical specifications for the design of automatic fire extinguishing and alarm systems.

Official publication

This code of practice uses normative references to the following standards:

GOST R 50588-93 Foaming agents for extinguishing fires. Are common technical requirements and test methods

GOST R 50680-94 Automatic water fire extinguishing installations. General technical requirements. Test methods

GOST R 50800-95 Automatic foam fire extinguishing installations. General technical requirements. Test methods

GOST R 50969-96 Automatic gas fire extinguishing installations. General technical requirements. Test methods

GOST R 51043—2002 Automatic water and foam fire extinguishing installations. Sprinklers. General technical requirements. Test methods

GOST R 51046—97 Fire fighting equipment. Fire extinguishing aerosol generators. Types and main parameters

GOST R 51049—2008 Fire fighting equipment. Firefighting pressure hoses. General technical requirements. Test methods

GOST R 51052—2002 Automatic water and foam fire extinguishing installations. Control nodes. General technical requirements. Test methods

GOST R 51057—2001 Fire fighting equipment. Fire extinguishers are portable. General technical requirements. Test methods

GOST 51091—97 Automatic powder fire extinguishing installations. Types and main parameters

GOST R 51115-97 Fire fighting equipment. Combined fire monitor trunks. General technical requirements. Test methods

GOST R 51737—2001 Automatic water and foam fire extinguishing installations. Detachable pipeline couplings. General technical requirements. Test methods

GOST R 51844—2009 Fire fighting equipment. Fire cabinets. General technical requirements. Test methods

GOST R 53278—2009 Fire fighting equipment. Fire shut-off valves. General technical requirements. Test methods

GOST R 53279—2009 Connecting heads for fire equipment. Types, main parameters and sizes

GOST R 53280.3 Automatic fire extinguishing installations. Fire extinguishing agents. Part 3. Gas extinguishing agents. Test methods

GOST R 53280.4—2009 Automatic fire extinguishing installations. Fire extinguishing agents. Part 4. General purpose fire extinguishing powders. General technical requirements. Test methods

GOST R 53281—2009 Automatic gas fire extinguishing installations. Modules and batteries. General technical requirements. Test methods

GOST R 53284—2009 Fire fighting equipment. Fire extinguishing aerosol generators. General technical requirements. Test methods

GOST R 53315—2009 Cable products. Fire safety requirements. Test methods GOST R 53325—2009 Fire fighting equipment. Fire automatic equipment. General technical requirements. Test methods

GOST R 53331—2009 Fire fighting equipment. Fireman's trunks are manual. General technical requirements. Test methods

GOST R 53329—2009 Robotic water and foam fire extinguishing installations. General technical requirements. Test methods

GOST 2.601—95 ESKD Operational documents

GOST 9.032—74 ESZKS Paint and varnish coatings. Groups, technical requirements and designations GOST 12.0.001—82 SSBT Basic provisions

GOST 12.0.004—90 SSBT Organization of occupational safety training. General provisions GOST 12.1.004-91 Fire safety. General requirements

GOST 12.1.005—88 SSBT General sanitary and hygienic requirements for air working area GOST 12.1.019—79 SSBT Electrical safety. General requirements and nomenclature of types of protection

GOST 12.1.030—81 SSBT Electrical safety. Protective grounding, grounding GOST 12.1.033-81 SSBT Fire safety. Terms and definitions GOST 12.1.044-89 SSBT Fire and explosion hazard of substances and materials. Nomenclature of indicators and methods for their determination

GOST 12.2.003—91 SSBT Production equipment. General safety requirements. GOST 12.2.007.0—75 SSBT Electrical products. General safety requirements GOST 12.2.047—86 SSBT Fire equipment. Terms and Definitions

GOST 12.2.072—98 Industrial robots. Robotic technological complexes. Safety requirements and test methods

GOST 12.3.046—91 SSBT Automatic fire extinguishing installations. General technical requirements

GOST 12.4.009—83 SSBT Fire equipment for the protection of objects. Main views, accommodation and service

GOST R 12.4.026—2001 SSBT Signal colors, safety signs and signal markings. Purpose and rules of use. General technical requirements and characteristics. Test methods

GOST 3262—75 Steel water-gas pipes. Technical specifications GOST 8732-78 Hot-deformed seamless steel pipes. Assortment GOST 8734-75 Seamless cold-deformed steel pipes. Assortment GOST 10704-91 Electric-welded straight-seam steel pipes. Assortment GOST 14202—69 Pipelines industrial enterprises. Identification markings, warning signs and markings

GOST 14254-96 Degrees of protection provided by shells

GOST 15150—69 Machines, instruments and others technical products. Versions for different climatic regions. Categories, operating, storage and transportation conditions regarding the impact of environmental climatic factors

GOST 21130-75 Electrical products. Grounding clamps and grounding signs. Design and dimensions

GOST 23511—79 Industrial radio interference from electrical devices, operated in residential buildings or connected to their electrical networks. Standards and measurement methods GOST 27331-87 Fire equipment. Fire classification

GOST 28130-89 Fire equipment. Fire extinguishers, fire extinguishing and fire alarm systems. Conventional graphic symbols

GOST 28338-89* Pipeline connections and fittings. The passages are conditional (nominal dimensions). Rows

Note - When using this set of rules, it is advisable to check the validity of reference standards, sets of rules and classifiers in the public information system - on the official website of the Federal Agency for Technical Regulation and Metrology on the Internet or using the annually published information index "National Standards", which is published on as of January 1 of the current year, and according to the corresponding monthly information indexes published in the current year. If the reference standard is replaced (changed), then when using this set of rules you should be guided by the replacing (changed) standard. If the reference standard is canceled without replacement, then the provision in which a reference is made to it is applied in the part that does not affect this reference.

3 Terms and definitions

In this set of rules, the following terms with corresponding definitions are used:

3.1 automatic start of a fire extinguishing installation: Start of the installation from its technical means without human intervention.

3.2 automatic fire extinguishing installation (AUP): A fire extinguishing installation that is automatically activated when the controlled fire factor(s) exceeds the established threshold values ​​in the protected area.

Note: SP 5.13130.2009 as amended No. 1 "Fire protection systems. Fire alarm and automatic fire extinguishing installations. Design standards and rules" replaced by SP 5.13130.2013.

SP 5.13130.2009 as amended No. 1 "Fire protection systems. Automatic fire alarm and fire extinguishing installations. Design standards and rules"

  1. Preface
  2. 1 area of ​​use
  3. 2. Normative references
  4. 3. Terms and definitions
  5. 4. General provisions
  6. 5. Water and foam fire extinguishing systems
  7. 6. Fire extinguishing installations with high expansion foam
  8. 7. Robotic fire complex
  9. 8. Gas fire extinguishing installations
  10. 9. Modular type powder fire extinguishing installations
  11. 10. Aerosol fire extinguishing installations
  12. 11. Autonomous fire extinguishing installations
  13. 12. Control equipment for fire extinguishing installations
  14. 13. Fire alarm systems
  15. 14. Interrelation of fire alarm systems with other systems and engineering equipment of objects
  16. 15. Power supply of fire alarm systems and fire extinguishing installations
  17. 16. Protective grounding and grounding. Safety requirements
  18. 17. General provisions taken into account when choosing fire automatic equipment
  19. Appendix A. List of buildings, structures, premises and equipment subject to protection by automatic fire extinguishing installations and automatic fire alarms. General provisions
    1. I. Buildings
    2. II. Facilities
    3. III. Premises
    4. IV. Equipment
  20. Appendix B Groups of premises (industrial and technological processes) according to the degree of fire hazard depending on their functional purpose and fire load of combustible materials
  21. Appendix B Methodology for calculating the parameters of the fire extinguishing system for surface fire extinguishing with water and low expansion foam
  22. Appendix D Methodology for calculating the parameters of high-expansion foam fire extinguishing installations
  23. Appendix D Initial data for calculating the mass of gaseous fire extinguishing agents
  24. Appendix E Methodology for calculating the mass of gas fire extinguishing agent for gas fire extinguishing installations when extinguishing by volumetric method
  25. Appendix G. Methodology for hydraulic calculation of low-pressure carbon dioxide fire extinguishing installations
  26. Appendix Z. Methodology for calculating the opening area for releasing excess pressure in rooms protected by gas fire extinguishing installations
  27. Appendix I. General provisions for the calculation of modular type powder fire extinguishing installations
  28. Appendix K Methodology for calculating automatic aerosol fire extinguishing installations
  29. Appendix L. Methodology for calculating excess pressure when supplying fire extinguishing aerosol to a room
  30. Appendix M Selection of types of fire detectors depending on the purpose of the protected premises and the type of fire load
  31. Appendix N. Installation locations of manual fire call points depending on the purpose of buildings and premises
  32. Appendix O. Determination of the set time for detecting a malfunction and eliminating it
  33. Appendix P Distances from the top point of the ceiling to the detector measuring element
  34. Appendix R Methods for increasing the reliability of a fire signal
  35. Bibliography

PREFACE

The goals and principles of standardization in the Russian Federation are established by the Federal Law of December 27, 202 No. 184-FZ “On Technical Regulation”, and the rules for applying sets of rules are established by the Decree of the Government of the Russian Federation “On the procedure for developing and approving sets of rules” dated November 19, 2008 No. 858.

Information on the set of rules SP 5.13130.2009 "Fire protection systems. Automatic fire alarm and fire extinguishing installations. Design standards and rules"

  • DEVELOPED BY FGU VNIIPO EMERCOM of Russia
  • INTRODUCED by the Technical Committee for Standardization TC 274 “Fire Safety”
  • APPROVED AND ENTERED INTO EFFECT by Order of the Ministry of Emergency Situations of Russia dated March 25, 2009 No. 175
  • REGISTERED by the Federal Agency for Technical Regulation and Metrology
  • INTRODUCED FOR THE FIRST TIME
  • Change No. 1 was introduced, approved and put into effect by order of the Ministry of Emergency Situations of Russia dated June 1, 2011 No. 274. The effective date of change No. 1 is June 20, 2011.

1 AREA OF USE

1.1 SP 5.13130.2009 "Fire protection systems. Fire alarm and automatic fire extinguishing installations. Design standards and rules" developed in accordance with Articles 42, 45, 46, 54, 83, 84, 91, 103, 104, 111 - 116 of the Federal Law dated July 22, 2008 No. 123-FZ “Technical Regulations on Fire Safety Requirements” is a regulatory document on fire safety in the field of standardization of voluntary use and establishes standards and rules for the design of automatic fire extinguishing and alarm systems.

1.2 SP 5.13130.2009 "Fire protection systems. Automatic fire alarm and fire extinguishing installations. Design standards and rules" applies to the design of automatic fire extinguishing and fire alarm installations for buildings and structures for various purposes, including those built in areas with special climatic and natural conditions. The need to use fire extinguishing and fire alarm systems is determined in accordance with Appendix A, standards, codes of practice and other documents approved in the prescribed manner.

1.3 SP 5.13130.2009 "Fire protection systems. Automatic fire alarm and fire extinguishing installations. Design standards and rules" does not apply to the design of automatic fire extinguishing and fire alarm installations:

  • buildings and structures designed according to special standards;
  • technological installations located outside buildings;
  • warehouse buildings with mobile shelving;
  • warehouse buildings for storing products in aerosol packaging;
  • warehouse buildings with a cargo storage height of more than 5.5 m.

1.4 SP 5.13130.2009 "Fire protection systems. Automatic fire alarm and fire extinguishing installations. Design standards and rules" does not apply to the design of fire extinguishing installations for extinguishing class D fires (according to GOST 27331), as well as chemically active substances and materials, including:

  • reacting with a fire extinguishing agent with an explosion (organoaluminum compounds, alkali metals);
  • decomposing upon interaction with a fire extinguishing agent with the release of flammable gases (organolithium compounds, lead azide, aluminum, zinc, magnesium hydrides);
  • interacting with a fire extinguishing agent with a strong exothermic effect (sulfuric acid, titanium chloride, thermite);
  • spontaneously combustible substances (sodium hydrosulfite, etc.).

1.5 SP 5.13130.2009 "Fire protection systems. Automatic fire alarm and fire extinguishing installations. Design standards and rules" can be used in the development of special technical specifications for the design of automatic fire extinguishing and alarm installations.

Other documents

SP 2.13130.2012 Fire protection systems. Ensuring the fire resistance of protected objects

DOC, 304.0 KB